{"id":4487,"date":"2026-09-22T09:00:00","date_gmt":"2026-09-22T09:00:00","guid":{"rendered":"https:\/\/www.paradigmcooling.co.za\/articles\/?p=4487"},"modified":"2026-09-22T09:00:00","modified_gmt":"2026-09-22T09:00:00","slug":"why-your-compressor-keeps-tripping-the-overload","status":"publish","type":"post","link":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/","title":{"rendered":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">A compressor that trips its overload again and again is usually not lying to you, and raising the dial is usually the wrong response. Six distinct faults produce the same symptom \u2014 the thermal element opens, the contactor drops out \u2014 and each leaves a different signature in a voltmeter and clamp meter reading. By the end of this article you&#8217;ll run through all six in order, know exactly which measurement separates each from the rest, and understand why treating the trip as the problem instead of the message destroys compressors.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Why the overload is usually telling the truth<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A thermal overload relay is a thermal model of the winding it protects: load current passes through a heating element wound around a bimetallic strip in each phase, the strip bends as it warms, and past a set deflection it opens a contact in the contactor coil circuit. Under IEC 60947-4-1, an overload set to nameplate FLA must not trip at 1.05 times setting within two hours, and must trip at 1.20 times within two hours. For an 18 A compressor that means it tolerates 18.9 A indefinitely and acts above 21.6 A \u2014 not oversensitive, doing exactly what it&#8217;s built to do.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Raising the setting to stop the tripping is the single most damaging habit in this trade. Insulation life halves for roughly every 10\u00b0C above rated temperature, and winding heating rises with the square of current. Raise an 18 A overload to 24 A and you allow (24 \u00f7 18)\u00b2 = 1.78 times the heat input the winding was designed for. The compressor fails in eight or eighteen months, by which point nobody connects the two events. Treat every trip as a measurement result, and work through the six causes below before touching the dial.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Safety note:<\/strong> every measurement below is taken with the circuit live \u2014 voltage at terminals under load, current on a clamp meter, voltage drop across a closed contactor pole. Use a CAT-rated meter appropriate to the panel, keep one hand clear where practical, and treat every live panel per your site&#8217;s OHS Act 85 of 1993 procedure.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The six causes, and the measurement that separates each<\/h2>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>#<\/th><th>Cause<\/th><th>What to measure<\/th><th>Signature that confirms it<\/th><\/tr><\/thead><tbody><tr><td>1<\/td><td>Low supply voltage<\/td><td>Line-to-line and line-to-neutral voltage under load<\/td><td>Below 360 V (three-phase) or 207 V (single-phase); current rises to compensate, torque falls<\/td><\/tr><tr><td>2<\/td><td>Voltage imbalance or phase loss<\/td><td>NEMA voltage imbalance across all line pairs<\/td><td>Imbalance above 2%, or one line near 0 V with the other two elevated<\/td><\/tr><tr><td>3<\/td><td>Pitted contactor pole<\/td><td>Voltage drop across each closed pole under load<\/td><td>One pole above 0.5 V while others read below 0.1 V<\/td><\/tr><tr><td>4<\/td><td>Mechanical load or seized bearing<\/td><td>Running current against nameplate FLA; insulation resistance<\/td><td>Current at or near locked rotor continuously; windings test electrically normal<\/td><\/tr><tr><td>5<\/td><td>Incorrect overload setting<\/td><td>Dial setting against nameplate FLA<\/td><td>Dial set below nameplate, or wrong trip class for the compressor type<\/td><\/tr><tr><td>6<\/td><td>Genuine winding failure<\/td><td>Winding resistance balance; insulation resistance to earth<\/td><td>Resistance imbalance beyond 5%, or insulation resistance near or below 1 M\u03a9<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 1: low supply voltage<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Starting torque in an induction motor varies with the square of applied voltage. Drop the supply from 230 V to 200 V (87% of nominal) and torque falls to 0.87\u00b2 = 0.756 \u2014 roughly 76% of rated. A compressor with margin to spare shrugs that off; one already marginal may simply not break away, humming and tripping on overload instead. On three-phase, expect 400 V \u00b110% (360-440 V) line-to-line and 230 V \u00b110% (207-253 V) line-to-neutral \u2014 outside that band, don&#8217;t expect normal starting or running behaviour.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">This is exactly the pattern seen around load shedding: voltage sags under heavy demand, and the surge of simultaneous reconnections after a stage lifts puts supply voltage below nominal at the moment compressors across a site try to restart together. A compressor that starts reliably alone and fails during a recovery window is often a voltage problem, not a compressor problem \u2014 confirm it with a meter at the terminals during the actual start attempt before condemning anything.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 2: voltage imbalance or phase loss<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Measure all three line-to-line voltages, average them, and express the largest single deviation from that average as a percentage of the average \u2014 the NEMA method. The limit is 2%. Above that, current imbalance in the motor runs at roughly 6 to 10 times the voltage imbalance percentage, because the negative-sequence component sees a very low rotor impedance. A 3.9% voltage imbalance predicts current imbalance somewhere between 23% and 39% \u2014 enough on its own to trip an overload with no fault in the compressor at all. Full detail on running this calculation is in our guide to <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/voltage-imbalance-on-three-phase-refrigeration\/\">measuring voltage imbalance on three-phase refrigeration<\/a>.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Phase loss is the acute version of the same fault: lose one line while the compressor runs and current in the remaining two phases rises to roughly 1.73 times normal, overheating windings within minutes. The signature is unmistakable \u2014 one line at or near 0 A with the other two high and roughly equal. Check upstream for a blown fuse, one contactor pole not closing, an open overload element, or a lost phase at the supply.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 3: a pitted contactor pole single-phasing the motor<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A contactor pole that has pitted or partially failed can either add resistance without fully opening, or fail to close at all \u2014 both produce a trip that looks electrically like a motor fault. Measure voltage drop across each closed pole with the load running at normal current: below 0.1 V per pole is healthy, 0.1-0.3 V means pitting has begun, 0.3-0.5 V is deteriorating fast, and above 0.5 V means replace now. A pole that has failed to make contact at all produces the same one-line-low signature as phase loss above, traced to the contactor rather than the supply. Cold resistance across a closed contact is not the test \u2014 a healthy contact is 1-5 m\u03a9, well below what a multimeter&#8217;s ohms range can resolve, so only a voltage-drop reading under load catches it. The full procedure is in our guide to <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/how-to-test-a-contactor-properly\/\">testing a contactor properly<\/a>.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 4: mechanical load or a seized bearing<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A mechanically seized compressor \u2014 a stuck scroll, a seized bearing, hydraulic lock from migrated oil or liquid refrigerant \u2014 draws current at or near locked rotor current continuously, because the rotor cannot turn, tripping the overload within seconds every time it&#8217;s reset. Isolated and cooled, winding resistance and insulation resistance both test normal, because the problem is not electrical. That distinction matters: a compressor condemned &#8220;electrically faulty&#8221; on this symptom alone, without a resistance and insulation check, is sometimes a sound motor bolted to a seized mechanism.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A lesser version of the same cause is a running compressor with current sitting persistently 15-30% above nameplate FLA, with supply voltage and superheat both confirmed normal \u2014 pointing to a mechanical drag or a partially shorted winding rather than an outright seizure, and worth investigating rather than dismissing as a nuisance trip.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 5: incorrect overload setting<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Set the dial to nameplate FLA, not to whatever number stops the tripping. A dial left at a previous compressor&#8217;s rating, or nudged down during a service, trips a perfectly healthy motor at normal running current. Trip class matters too: Class 10 is the default for hermetic and semi-hermetic compressors, which accelerate to speed in under two seconds and hold at 7.2 times set current for only 2-10 seconds from cold. Class 20 or 30 belong on high-inertia loads \u2014 open-drive and screw compressors, large flywheels. A Class 10 relay tripping on every start is often correctly protecting a start that&#8217;s taking too long, not an incorrectly rated device.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Overloads on a compressor should always be manual reset, never automatic. An automatic-reset overload recloses once the bimetal cools, typically after 2-5 minutes, restarting a stalled or faulted compressor into the same condition every few minutes at locked-rotor current \u2014 5 to 8 times FLA \u2014 until the windings carbonise. It also destroys the evidence that it tripped, which is exactly the evidence needed to work through the other five causes.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Cause 6: genuine winding failure<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">This is the cause to confirm last, not first, and only with two independent tests. Measure resistance across all three winding pairs (three-phase) and require them within 5% of each other, or measure C-R and C-S on a single-phase compressor and check the arithmetic identity C-S + C-R = S-R. Then test insulation resistance winding-to-earth at 500 V DC (230 V equipment) or 1000 V DC (400 V equipment): reject anything below the absolute floor of 1 M\u03a9, and treat a healthy reading as well above 100 M\u03a9. A shorted turn is genuinely hard to catch on resistance alone \u2014 a couple of percent of turns shorted barely moves the reading \u2014 so a compressor with balanced, in-tolerance resistance and clean insulation resistance is very likely sound even if it has been tripping repeatedly. The fault, in that case, is one of the other five causes, not the winding.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Final Thoughts<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">In 28 years of chasing overload trips, the pattern repeats: a technician replaces the compressor, the new one trips within the hour, and only then does someone reach for a voltmeter. Work the six causes in the order given here \u2014 supply voltage, imbalance and phase loss, the contactor, the mechanical load, the setting itself, and only then the winding \u2014 and a six-minute test sequence with a clamp meter and a voltmeter separates a lug, a pole, or a bad phase from an actual dead compressor almost every time. The full method behind every one of these tests is in the <a href=\"https:\/\/www.paradigmcooling.co.za\/hvacr-learning-library\/hvacr-electrical-diagnostics-the-complete-guide-to-electrical-troubleshooting-testing-and-fault-finding\/\">complete guide to electrical troubleshooting and fault-finding<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>A compressor that trips its overload again and again is usually not lying to you, and raising the dial is usually the wrong response. Six [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[36,18],"tags":[],"class_list":["post-4487","post","type-post","status-publish","format-standard","hentry","category-electrical-diagnostics","category-technical"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.5 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;<\/title>\n<meta name=\"description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"og:description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/\" \/>\n<meta property=\"og:site_name\" content=\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/Paradigm-Cooling\" \/>\n<meta property=\"article:published_time\" content=\"2026-09-22T09:00:00+00:00\" \/>\n<meta name=\"author\" content=\"Paradigm Cooling\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:site\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Paradigm Cooling\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"8 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/\"},\"author\":{\"name\":\"Paradigm Cooling\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"headline\":\"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart\",\"datePublished\":\"2026-09-22T09:00:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/\"},\"wordCount\":1554,\"commentCount\":0,\"articleSection\":[\"Electrical Diagnostics\",\"Technical\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/\",\"name\":\"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\"},\"datePublished\":\"2026-09-22T09:00:00+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"description\":\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/22\\\/why-your-compressor-keeps-tripping-the-overload\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\",\"name\":\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"description\":\"Engineered Comfort\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\",\"name\":\"Paradigm Cooling\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"url\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"contentUrl\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"caption\":\"Paradigm Cooling\"},\"sameAs\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\"],\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/","og_locale":"en_US","og_type":"article","og_title":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","og_description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","og_url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/","og_site_name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","article_publisher":"https:\/\/www.facebook.com\/Paradigm-Cooling","article_published_time":"2026-09-22T09:00:00+00:00","author":"Paradigm Cooling","twitter_card":"summary_large_image","twitter_creator":"@ParadigmCooling","twitter_site":"@ParadigmCooling","twitter_misc":{"Written by":"Paradigm Cooling","Est. reading time":"8 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/#article","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/"},"author":{"name":"Paradigm Cooling","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"headline":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart","datePublished":"2026-09-22T09:00:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/"},"wordCount":1554,"commentCount":0,"articleSection":["Electrical Diagnostics","Technical"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/","url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/","name":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website"},"datePublished":"2026-09-22T09:00:00+00:00","author":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","breadcrumb":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/22\/why-your-compressor-keeps-tripping-the-overload\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.paradigmcooling.co.za\/articles\/"},{"@type":"ListItem","position":2,"name":"Why Your Compressor Keeps Tripping the Overload: Six Causes and How to Tell Them Apart"}]},{"@type":"WebSite","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website","url":"https:\/\/www.paradigmcooling.co.za\/articles\/","name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Engineered Comfort","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.paradigmcooling.co.za\/articles\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02","name":"Paradigm Cooling","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","url":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","contentUrl":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","caption":"Paradigm Cooling"},"sameAs":["https:\/\/www.paradigmcooling.co.za\/articles"],"url":"https:\/\/www.paradigmcooling.co.za\/articles\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4487","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/comments?post=4487"}],"version-history":[{"count":1,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4487\/revisions"}],"predecessor-version":[{"id":4866,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4487\/revisions\/4866"}],"wp:attachment":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/media?parent=4487"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/categories?post=4487"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/tags?post=4487"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}