{"id":4488,"date":"2026-09-24T09:00:00","date_gmt":"2026-09-24T09:00:00","guid":{"rendered":"https:\/\/www.paradigmcooling.co.za\/articles\/?p=4488"},"modified":"2026-09-24T09:00:00","modified_gmt":"2026-09-24T09:00:00","slug":"what-load-shedding-does-to-refrigeration-equipment","status":"publish","type":"post","link":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/","title":{"rendered":"What Load Shedding Does to Your Refrigeration Equipment"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">Every stage of load shedding ends the same way for a cold room or condensing unit: the power comes back, the compressor restarts, and it looks like nothing happened. What actually happens electrically during that restart \u2014 voltage sag, high inrush current, a compressor starting against pressure it hasn&#8217;t had time to equalise, contactor contacts absorbing an arc they weren&#8217;t sized for \u2014 is invisible unless you measure it, and it is the reason equipment on load-shedding sites fails years earlier than the same equipment on stable supply. By the end of this article you&#8217;ll understand exactly what the restart cycle does to a compressor and its contactor, and which three protections actually stop the damage rather than just delaying it.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Happens Electrically the Moment Power Returns<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">When supply is restored after an outage, every compressor on that feeder \u2014 not just yours \u2014 restarts at the same instant. Two things happen together, and they compound each other.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Every compressor draws inrush current during restoration<\/strong>, typically <strong>five to seven times its full-load current<\/strong>, exactly as it would on any cold start. On a long feeder carrying a whole neighbourhood&#8217;s simultaneous restart, the combined demand produces a deep voltage sag \u2014 often <strong>180 V to 200 V for several seconds<\/strong> on a nominal 230 V supply, well below the statutory \u00b110% tolerance band of 207\u2013253 V.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">That sag matters because motor starting torque falls with the <strong>square<\/strong> of applied voltage, not linearly. A supply sagging to 200 V (87% of rated) delivers only about 76% of rated starting torque; at 180 V (78% of rated) torque falls to around 61%. Every compressor on that feeder is therefore trying to start on a fraction of its rated torque, at the exact moment it also needs maximum torque to break away against head pressure. Many simply fail to start, trip on locked rotor, and sit waiting for the next reset.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Restoration voltage<\/th><th>% of 230 V rated<\/th><th>Approximate starting torque<\/th><\/tr><\/thead><tbody><tr><td>200 V<\/td><td>87%<\/td><td>~76% of rated<\/td><\/tr><tr><td>190 V<\/td><td>83%<\/td><td>~68% of rated<\/td><\/tr><tr><td>180 V<\/td><td>78%<\/td><td>~61% of rated<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Repeated Restarts and Short Cycling<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A compressor design figure of around six starts per hour assumes normal thermostat cycling with time to cool down between starts. Load shedding does not respect that figure. A site running four stages of load shedding a day, each with a trip-and-reset cycle before the compressor settles into a stable run, can push a compressor to <strong>fourteen starts an hour or more<\/strong> \u2014 more than double its design limit.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Every one of those starts passes locked-rotor current \u2014 commonly on the order of <strong>140 A on a 24 A compressor<\/strong>, in line with the 5\u20137 times FLA figure above \u2014 through the windings and the contactor&#8217;s contact tips. Windings sized for occasional starting current absorb thermal soaks faster than they dissipate the heat between cycles, shortening insulation life before any single event looks like a failure. The contactor pays a more visible price: repeated arcing at each make and break erodes the silver contact surface, raising contact resistance, which raises heat at that pole, which accelerates the erosion further \u2014 a wear cycle covered in <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/how-to-test-a-contactor-properly\/\">how to test a contactor properly<\/a>, including the voltage-drop measurement that catches a contactor already on this path before it welds shut or burns a pole open.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Starting Against Head Pressure<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A scroll or reciprocating compressor that stops abruptly has full discharge pressure on one side of the system and suction pressure on the other. That differential needs time to bleed away and equalise before the next start \u2014 <strong>typically 3 to 5 minutes<\/strong>. Restore power inside that window and the motor is starting against a pressure differential it was never designed to break away against: effectively a locked-rotor start regardless of how healthy the motor is.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Combine that with the voltage sag above \u2014 reduced torque exactly when maximum torque is needed \u2014 and a compressor that would start without complaint on a stable supply, with equalised pressures, stalls repeatedly during a load-shedding evening. Each stall is another full locked-rotor current event through windings and contacts that have already absorbed several that hour.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Inverter Equipment: A Different Kind of Stress<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Fixed-speed compressors aren&#8217;t the only casualties. Inverter-driven compressors and fans carry a DC bus \u2014 a bank of electrolytic capacitors storing the rectified supply voltage \u2014 and every restart charges that bus from zero, drawing a substantial inrush current through the rectifier into the capacitor bank. Where load shedding forces several outages and restarts in a single day, that charge-discharge cycle repeats every time.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Electrolytic capacitors have a finite number of charge cycles, and their service life shortens with heat and repeated stress \u2014 the same restart pattern that erodes a contactor&#8217;s contacts on fixed-speed equipment accelerates capacitor ageing on inverter equipment instead. A <strong>restart delay of 3 to 5 minutes<\/strong> after supply returns reduces this stress the same way it protects a fixed-speed compressor, and confirming this delay is fitted and correctly set on inverter equipment is worth checking specifically, not assumed because the equipment is newer.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The Practical Protections<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Three measures address the mechanisms above directly, and none of them are expensive relative to a replaced compressor or a burnt contactor.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Protection<\/th><th>What it does<\/th><th>Typical setting<\/th><\/tr><\/thead><tbody><tr><td>Phase-failure relay<\/td><td>Prevents the contactor closing on phase loss, phase reversal, or voltage outside the acceptable window<\/td><td>Under-voltage trip around 360 V, over-voltage trip around 440 V (phase-to-phase, 400 V systems)<\/td><\/tr><tr><td>Restart delay \/ anti-short-cycle timer<\/td><td>Holds the compressor off supply after any stop, giving pressures time to equalise and avoiding an instant reconnect into a voltage sag<\/td><td>3 to 5 minutes minimum per unit; stagger adjacent units (e.g. 3, 4 and 5 minutes) so a feeder&#8217;s units don&#8217;t all restart in the same window<\/td><\/tr><tr><td>Surge protection<\/td><td>Limits transient over-voltage on restoration and switching events from reaching sensitive electronics and DC bus capacitors<\/td><td>Sized to the panel&#8217;s incoming supply, fitted at the origin of the installation<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">The restart delay is doing the most work of the three: it addresses both the pressure-equalisation problem and, by staggering when each unit reconnects, reduces how deep the feeder-wide voltage sag gets in the first place, since not every compressor on the line is inrushing at the same second.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Why a Poorly Regulated Generator Can Be Worse Than No Power at All<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A generator brought in to bridge load-shedding outages solves the immediate problem \u2014 the plant keeps running \u2014 but poor voltage regulation can put equipment through worse stress than simply waiting for utility power. Utility supply, even sagging under restoration load, stays reasonably bounded near nominal; an undersized or poorly regulated generator can swing well outside the \u00b110% tolerance band in both directions as its load changes \u2014 under-voltage starting a large compressor, over-voltage once that load drops off. Both mechanisms above (torque loss on under-voltage, capacitor and insulation stress on over-voltage) apply to a generator exactly as they do to the grid, more often and more severely.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Before commissioning any generator changeover, confirm phase rotation on the generator supply specifically \u2014 it is not guaranteed to match utility rotation, and a reversed generator runs every scroll compressor on site backward, with no obvious symptom beyond a loud rattle and a compressor that develops no pressure differential at all. Check it with a phase-sequence meter before you rely on generator power to run refrigeration overnight.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Safety note:<\/strong> any work around a generator changeover involves confirming the changeover switch genuinely isolates the utility side before the generator is live, and applying earths wherever a generator or inverter could back-feed, per your isolation procedure under the OHS Act 85 of 1993 and SANS 10142-1. Never assume a changeover switch is working correctly without proving it.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">For Business Owners: What This Actually Costs<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">If you run a cold room or a bank of condensing units through regular load shedding without these protections, the cost doesn&#8217;t show up as a single event \u2014 it shows up as compressors and contactors failing years ahead of schedule, on equipment that &#8220;was working fine&#8221; the week before. A replaced compressor and callout costs considerably more than a phase-failure relay and restart timer fitted once, and the protections work every load-shedding cycle rather than once. If a site has replaced the same compressor more than once in a year, the restart cycle itself \u2014 not bad luck with parts \u2014 is very often the cause, and it&#8217;s worth checking for <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/voltage-imbalance-on-three-phase-refrigeration\/\">voltage imbalance on the three-phase supply<\/a> at the same time, since a marginal imbalance a compressor tolerates on a stable supply becomes a much bigger problem stacked on repeated restoration sags.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Final Thoughts<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Load shedding doesn&#8217;t damage refrigeration equipment through any single dramatic event \u2014 it damages it through repetition: inrush current at five to seven times FLA on every restart, voltage sag during restoration cutting starting torque to roughly 61\u201376% of rated, compressors starting against pressure that hasn&#8217;t had 3 to 5 minutes to equalise, and contactor contacts absorbing an arc every single time. A phase-failure relay, a properly set restart delay, and surge protection at the panel address these mechanisms directly and cost a fraction of what a burnt-out compressor or welded contactor costs to replace. The full electrical picture behind these numbers \u2014 and how to verify a site&#8217;s specific readings against them \u2014 is in our <a href=\"https:\/\/www.paradigmcooling.co.za\/hvacr-learning-library\/hvacr-electrical-diagnostics-the-complete-guide-to-electrical-troubleshooting-testing-and-fault-finding\/\">guide to electrical troubleshooting and testing<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Every stage of load shedding ends the same way for a cold room or condensing unit: the power comes back, the compressor restarts, and it [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[36,18],"tags":[],"class_list":["post-4488","post","type-post","status-publish","format-standard","hentry","category-electrical-diagnostics","category-technical"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.5 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;<\/title>\n<meta name=\"description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"og:description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/\" \/>\n<meta property=\"og:site_name\" content=\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/Paradigm-Cooling\" \/>\n<meta property=\"article:published_time\" content=\"2026-09-24T09:00:00+00:00\" \/>\n<meta name=\"author\" content=\"Paradigm Cooling\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:site\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Paradigm Cooling\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"7 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/\"},\"author\":{\"name\":\"Paradigm Cooling\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"headline\":\"What Load Shedding Does to Your Refrigeration Equipment\",\"datePublished\":\"2026-09-24T09:00:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/\"},\"wordCount\":1517,\"commentCount\":0,\"articleSection\":[\"Electrical Diagnostics\",\"Technical\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/\",\"name\":\"What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\"},\"datePublished\":\"2026-09-24T09:00:00+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"description\":\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/09\\\/24\\\/what-load-shedding-does-to-refrigeration-equipment\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"What Load Shedding Does to Your Refrigeration Equipment\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\",\"name\":\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"description\":\"Engineered Comfort\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\",\"name\":\"Paradigm Cooling\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"url\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"contentUrl\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"caption\":\"Paradigm Cooling\"},\"sameAs\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\"],\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/","og_locale":"en_US","og_type":"article","og_title":"What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","og_description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","og_url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/","og_site_name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","article_publisher":"https:\/\/www.facebook.com\/Paradigm-Cooling","article_published_time":"2026-09-24T09:00:00+00:00","author":"Paradigm Cooling","twitter_card":"summary_large_image","twitter_creator":"@ParadigmCooling","twitter_site":"@ParadigmCooling","twitter_misc":{"Written by":"Paradigm Cooling","Est. reading time":"7 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/#article","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/"},"author":{"name":"Paradigm Cooling","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"headline":"What Load Shedding Does to Your Refrigeration Equipment","datePublished":"2026-09-24T09:00:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/"},"wordCount":1517,"commentCount":0,"articleSection":["Electrical Diagnostics","Technical"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/","url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/","name":"What Load Shedding Does to Your Refrigeration Equipment - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website"},"datePublished":"2026-09-24T09:00:00+00:00","author":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","breadcrumb":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/09\/24\/what-load-shedding-does-to-refrigeration-equipment\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.paradigmcooling.co.za\/articles\/"},{"@type":"ListItem","position":2,"name":"What Load Shedding Does to Your Refrigeration Equipment"}]},{"@type":"WebSite","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website","url":"https:\/\/www.paradigmcooling.co.za\/articles\/","name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Engineered Comfort","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.paradigmcooling.co.za\/articles\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02","name":"Paradigm Cooling","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","url":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","contentUrl":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","caption":"Paradigm Cooling"},"sameAs":["https:\/\/www.paradigmcooling.co.za\/articles"],"url":"https:\/\/www.paradigmcooling.co.za\/articles\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4488","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/comments?post=4488"}],"version-history":[{"count":1,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4488\/revisions"}],"predecessor-version":[{"id":4867,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4488\/revisions\/4867"}],"wp:attachment":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/media?parent=4488"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/categories?post=4488"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/tags?post=4488"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}