{"id":4495,"date":"2026-10-10T09:00:00","date_gmt":"2026-10-10T09:00:00","guid":{"rendered":"https:\/\/www.paradigmcooling.co.za\/articles\/?p=4495"},"modified":"2026-10-10T09:00:00","modified_gmt":"2026-10-10T09:00:00","slug":"why-your-txv-is-hunting","status":"publish","type":"post","link":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/","title":{"rendered":"Why Your TXV Is Hunting, and How to Confirm It"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">A hunting TXV oscillates the evaporator between overfeeding and starving instead of settling on a stable superheat, and the fix depends entirely on which of several distinct causes is behind it \u2014 most of which have nothing wrong with the valve itself. This article gives you the readings that confirm hunting rather than a genuinely unstable load, the checklist of causes in the order worth working through, and the tests that confirm a valve is actually faulty before you replace a part that was never the problem.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Hunting Looks Like on the Gauges<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A stable TXV holds superheat within about \u00b11 K of target once the system has settled, with slow, small drift as ambient or load shifts gradually over minutes. A hunting valve instead shows a repeating swing of 3\u20136 K or more above and below target, cycling every 30 to 90 seconds, sometimes faster. Suction pressure oscillates in step with it \u2014 you&#8217;ll see the low-side gauge needle visibly moving up and down rather than sitting steady, often by 50\u2013150 kPa through each cycle. If you watch superheat swing from 2 K to 9 K and back to 2 K within two minutes, repeatedly, that is hunting, not a load change.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Build a Temperature Log, Don&#8217;t Trust a Single Reading<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">A single snapshot reading can land anywhere in the swing and look like a normal, in-range superheat by coincidence. Log suction line temperature and suction pressure at 15\u201330 second intervals for at least 5 minutes before you draw a conclusion:<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Time (seconds)<\/th><th>Suction temp (\u00b0C)<\/th><th>Sat. temp at suction pressure (\u00b0C)<\/th><th>Superheat (K)<\/th><\/tr><\/thead><tbody><tr><td>0<\/td><td>8.5<\/td><td>4.0<\/td><td>4.5<\/td><\/tr><tr><td>30<\/td><td>11.0<\/td><td>3.5<\/td><td>7.5<\/td><\/tr><tr><td>60<\/td><td>6.5<\/td><td>4.5<\/td><td>2.0<\/td><\/tr><tr><td>90<\/td><td>10.5<\/td><td>3.5<\/td><td>7.0<\/td><\/tr><tr><td>120<\/td><td>6.0<\/td><td>4.5<\/td><td>1.5<\/td><\/tr><tr><td>150<\/td><td>10.0<\/td><td>4.0<\/td><td>6.0<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">A target of 6 K on this system should hold within roughly 5\u20137 K once settled. This log shows superheat cycling between 1.5 K and 7.5 K every 60\u201390 seconds \u2014 a 6 K swing, well beyond normal drift \u2014 which confirms hunting rather than a marginal but stable reading.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The Checklist of Causes, in the Order Worth Checking<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Work through these in order \u2014 the first three catch the majority of hunting calls and cost nothing but time, while the last two require parts or a valve change:<\/p>\n\n\n\n<ol class=\"wp-block-list\"><li><strong>Bulb clamping and contact.<\/strong> A loose or poorly clamped bulb responds slowly and inconsistently to line temperature changes, which is itself enough to induce hunting even on a perfectly good valve.<\/li><li><strong>Bulb insulation.<\/strong> An uninsulated bulb senses ambient air temperature as well as line temperature, feeding the valve a signal that swings with the room or plant space rather than tracking refrigerant state alone.<\/li><li><strong>Bulb location on the line.<\/strong> Wrong clamp position relative to the pipe&#8217;s cross-section changes what the bulb actually senses.<\/li><li><strong>External equaliser line blocked or routed incorrectly.<\/strong> A blocked equaliser prevents the valve from correctly sensing evaporator outlet pressure, and it will overreact or underreact to changes.<\/li><li><strong>Moisture or debris in the valve body or inlet screen.<\/strong> Partial blockage causes erratic flow that looks exactly like hunting on the gauges.<\/li><li><strong>Loss of bulb charge.<\/strong> A bulb that has lost some of its internal charge responds weakly and unpredictably to temperature changes rather than proportionally.<\/li><li><strong>Valve oversized or misapplied for the load.<\/strong> An oversized valve has too much capacity relative to the evaporator&#8217;s actual demand and naturally overshoots and corrects, overshoots and corrects.<\/li><li><strong>Low or unstable load on the evaporator.<\/strong> Airflow well below rated CFM, or a load that&#8217;s cycling on its own (a door opening repeatedly, a defrost cycle interacting badly with the valve), can produce a genuinely unstable superheat that isn&#8217;t a valve fault at all.<\/li><\/ol>\n\n\n\n<h2 class=\"wp-block-heading\">Bulb Positioning and Insulation: Check These First<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">These two items alone account for a large share of hunting complaints, and they take minutes to inspect properly.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Position.<\/strong> For a horizontal suction line under about 22 mm outside diameter, the bulb should be clamped at the 10 o&#8217;clock or 2 o&#8217;clock position \u2014 never at the very top, where vapour can pool and give a lagged reading, and never at the bottom, where oil and any residual liquid distort the sensed temperature. Confirm the clamp is tight enough that the bulb has genuine metal-to-metal contact along its full length, not just touching at one point. For larger lines or vertical runs, follow the valve manufacturer&#8217;s specific mounting guidance rather than defaulting to the small-line convention.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Insulation.<\/strong> The bulb and its clamp must be wrapped in closed-cell insulation extending at least 4\u20135 cm past the clamp in both directions, sealed so ambient air cannot reach the pipe surface under the bulb. An uninsulated bulb in a plant room running 3\u20135 K above the suction line temperature will read a blended signal that neither matches line temperature nor stays consistent as room conditions shift through the day \u2014 which is functionally identical to hunting on the gauges even though the valve itself is fine.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Confirming the Valve Itself Is Faulty<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Don&#8217;t replace a valve on the strength of a hunting symptom alone \u2014 confirm the fault is actually in the valve using these checks, in order:<\/p>\n\n\n\n<ol class=\"wp-block-list\"><li><strong>Re-check bulb clamping, position and insulation first<\/strong>, and re-run your temperature log after correcting any of them. A large share of hunting calls resolve at this step alone, with no further action needed.<\/li><li><strong>Inspect and clear the external equaliser line.<\/strong> Confirm it&#8217;s connected to the correct sensing point (typically 15\u201320 cm downstream of the bulb location) and isn&#8217;t kinked, plugged, or accidentally cross-connected.<\/li><li><strong>Perform a bulb response test.<\/strong> With the system running and superheat logged as a baseline, warm the bulb by hand or with a warm cloth. A functioning valve should respond by opening further \u2014 suction pressure rising and superheat falling \u2014 within about 30\u201360 seconds. Then let the bulb cool back to line temperature (or apply a cold pack briefly) and confirm the valve throttles back, superheat rising again within a similar window. A valve that doesn&#8217;t respond to a clear bulb temperature change in either direction has a genuine mechanical or charge fault.<\/li><li><strong>Check for a frosted or sweating valve body<\/strong> with the inlet screen and strainer inspected for moisture or particulate blockage, since a partially blocked screen produces symptoms indistinguishable from a bad bulb without inspection.<\/li><li><strong>Confirm valve sizing against design tonnage and pressure drop<\/strong>, using the manufacturer&#8217;s selection chart \u2014 an oversized valve installed on a smaller-than-rated load will hunt structurally, and no amount of adjustment or bulb correction fixes a sizing error.<\/li><\/ol>\n\n\n\n<h2 class=\"wp-block-heading\">When to Replace vs Reposition<\/h2>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Finding from the checks above<\/th><th>Action<\/th><\/tr><\/thead><tbody><tr><td>Bulb loose, poorly clamped, or uninsulated<\/td><td>Reclamp and insulate correctly, re-log \u2014 no valve replacement<\/td><\/tr><tr><td>Bulb in wrong position on the pipe<\/td><td>Reposition to 10\/2 o&#8217;clock (small lines), re-log<\/td><\/tr><tr><td>Equaliser blocked or misrouted<\/td><td>Clear or reroute, re-log<\/td><\/tr><tr><td>Bulb responds correctly to hand-warming and cooling within 30\u201360 seconds<\/td><td>Valve mechanism and charge are sound \u2014 look elsewhere (load, airflow, sizing)<\/td><\/tr><tr><td>Bulb shows no response, or a sluggish, weak response, to a clear temperature change<\/td><td>Bulb charge loss or mechanical fault confirmed \u2014 replace the valve<\/td><\/tr><tr><td>Valve confirmed correctly clamped, insulated, positioned and responsive, but capacity exceeds the evaporator&#8217;s rated load<\/td><td>Valve is oversized for the application \u2014 replace with correctly sized unit, not a repeat of the same part<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Final Thoughts<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">TXV hunting has a clear, checkable order of causes, and the two most common ones \u2014 bulb clamping and bulb insulation \u2014 cost nothing to fix and should be ruled out before you suspect the valve mechanism itself. Confirm a genuine valve fault with a bulb response test rather than replacing on the strength of an oscillating gauge alone. For the measurement technique this diagnostic depends on, see <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/how-to-measure-superheat-step-by-step\/\">how to measure superheat step by step<\/a>, and for how a fixed orifice system&#8217;s superheat behaves without a valve controlling it at all, see <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/target-superheat-for-fixed-orifice-systems\/\">target superheat for fixed orifice systems<\/a>. The full diagnostic framework is covered in the <a href=\"https:\/\/www.paradigmcooling.co.za\/hvacr-learning-library\/understanding-superheat-and-subcooling-the-complete-guide-to-refrigerant-charging-diagnostics-and-hvacr-system-performance\/\">complete guide to superheat and subcooling<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>A hunting TXV oscillates the evaporator between overfeeding and starving instead of settling on a stable superheat, and the fix depends entirely on which of [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[19,37],"tags":[],"class_list":["post-4495","post","type-post","status-publish","format-standard","hentry","category-refrigeration","category-superheat-and-subcooling"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.6 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;<\/title>\n<meta name=\"description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"og:description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/\" \/>\n<meta property=\"og:site_name\" content=\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/Paradigm-Cooling\" \/>\n<meta property=\"article:published_time\" content=\"2026-10-10T09:00:00+00:00\" \/>\n<meta name=\"author\" content=\"Paradigm Cooling\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:site\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Paradigm Cooling\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"6 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/\"},\"author\":{\"name\":\"Paradigm Cooling\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"headline\":\"Why Your TXV Is Hunting, and How to Confirm It\",\"datePublished\":\"2026-10-10T09:00:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/\"},\"wordCount\":1285,\"commentCount\":0,\"articleSection\":[\"Refrigeration\",\"Superheat and Subcooling\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/\",\"name\":\"Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\"},\"datePublished\":\"2026-10-10T09:00:00+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"description\":\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/10\\\/why-your-txv-is-hunting\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Why Your TXV Is Hunting, and How to Confirm It\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\",\"name\":\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"description\":\"Engineered Comfort\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\",\"name\":\"Paradigm Cooling\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"url\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"contentUrl\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"caption\":\"Paradigm Cooling\"},\"sameAs\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\"],\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/","og_locale":"en_US","og_type":"article","og_title":"Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","og_description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","og_url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/","og_site_name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","article_publisher":"https:\/\/www.facebook.com\/Paradigm-Cooling","article_published_time":"2026-10-10T09:00:00+00:00","author":"Paradigm Cooling","twitter_card":"summary_large_image","twitter_creator":"@ParadigmCooling","twitter_site":"@ParadigmCooling","twitter_misc":{"Written by":"Paradigm Cooling","Est. reading time":"6 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/#article","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/"},"author":{"name":"Paradigm Cooling","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"headline":"Why Your TXV Is Hunting, and How to Confirm It","datePublished":"2026-10-10T09:00:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/"},"wordCount":1285,"commentCount":0,"articleSection":["Refrigeration","Superheat and Subcooling"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/","url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/","name":"Why Your TXV Is Hunting, and How to Confirm It - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website"},"datePublished":"2026-10-10T09:00:00+00:00","author":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","breadcrumb":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/10\/why-your-txv-is-hunting\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.paradigmcooling.co.za\/articles\/"},{"@type":"ListItem","position":2,"name":"Why Your TXV Is Hunting, and How to Confirm It"}]},{"@type":"WebSite","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website","url":"https:\/\/www.paradigmcooling.co.za\/articles\/","name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Engineered Comfort","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.paradigmcooling.co.za\/articles\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02","name":"Paradigm Cooling","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","url":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","contentUrl":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","caption":"Paradigm Cooling"},"sameAs":["https:\/\/www.paradigmcooling.co.za\/articles"],"url":"https:\/\/www.paradigmcooling.co.za\/articles\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4495","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/comments?post=4495"}],"version-history":[{"count":1,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4495\/revisions"}],"predecessor-version":[{"id":4882,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4495\/revisions\/4882"}],"wp:attachment":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/media?parent=4495"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/categories?post=4495"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/tags?post=4495"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}