{"id":4496,"date":"2026-10-13T09:00:00","date_gmt":"2026-10-13T09:00:00","guid":{"rendered":"https:\/\/www.paradigmcooling.co.za\/articles\/?p=4496"},"modified":"2026-10-13T09:00:00","modified_gmt":"2026-10-13T09:00:00","slug":"superheat-readings-on-r32-and-r410a","status":"publish","type":"post","link":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/","title":{"rendered":"Superheat and Subcooling on R-32 and R-410A: What Changes"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">R-32 is replacing R-410A across much of the split and light commercial market, and the good news for a working technician is that the diagnostic method doesn&#8217;t change \u2014 but two things do change enough to catch you out if you carry R-410A habits across without checking: discharge temperature runs meaningfully higher on R-32, and R-32&#8217;s mild flammability changes how you handle leaks, recovery, and service work. This article separates what stays identical between the two refrigerants from what genuinely changes, with the numbers that matter for compressor protection and safe handling.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">The Core Method Doesn&#8217;t Change<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Superheat is still suction line temperature minus the saturation temperature at suction pressure, and subcooling is still the saturation temperature at liquid line pressure minus liquid line temperature. The targets you&#8217;re charging to \u2014 typically 4\u20138 K superheat and 5\u201310 K subcooling depending on the equipment, exact figures from the manufacturer&#8217;s data \u2014 are set by the equipment design, not by which of these two refrigerants is inside it. If you know how to take these readings correctly on one, you already know how to take them on the other; the pressure gauge you read the saturation temperature off just needs to be scaled or referenced for the refrigerant in the system.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Glide: Why Neither of These Needs Dew and Bubble Point Math<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">This is worth stating plainly because it&#8217;s a common point of confusion once technicians start working with blends generally.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Refrigerant<\/th><th>Composition<\/th><th>Glide<\/th><th>Field treatment<\/th><\/tr><\/thead><tbody><tr><td>R-32<\/td><td>Single component<\/td><td>None (0 K)<\/td><td>Saturation temperature is one value at a given pressure \u2014 read it straight off the chart<\/td><\/tr><tr><td>R-410A<\/td><td>Near-azeotropic blend (R-32\/R-125)<\/td><td>Very small, well under 0.2 K<\/td><td>Commonly treated as negligible \u2014 use the single saturation value your gauge or chart gives<\/td><\/tr><tr><td>R-407C (for comparison)<\/td><td>Zeotropic blend with significant glide<\/td><td>Roughly 5\u20137 K<\/td><td>Must use the dew point for superheat and the bubble point for subcooling \u2014 using a single saturation value produces a real error<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">R-32 has zero glide because it&#8217;s a single compound, and R-410A&#8217;s glide is small enough that it&#8217;s not something you need to correct for in normal field charging and diagnostic work. Neither requires the dew\/bubble point split that a genuinely glide-heavy blend like R-407C demands. If you&#8217;re moving onto R-407C equipment, that&#8217;s the point where the calculation actually changes \u2014 not between R-32 and R-410A.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Pressure-Temperature Relationship: Close Enough Not to Trip You Up<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">R-32 and R-410A have closely matched pressure-temperature curves \u2014 R-32&#8217;s saturation pressure at a given temperature runs close to R-410A&#8217;s, generally within about 5% across the normal operating range. This is expected, since R-410A is itself a 50\/50 blend of R-32 and R-125. Practically, this means your existing pressure-temperature reference habits and rough mental checks transfer reasonably well between the two, but always pull the correct saturation temperature off the chart or electronic gauge set for the refrigerant actually in the system \u2014 don&#8217;t estimate one from memory of the other when precision matters for a subcooling or superheat calculation.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Discharge Temperature: The Number That Actually Changes<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">This is the difference that matters most for compressor protection. R-32 runs noticeably hotter at discharge than R-410A under comparable operating conditions \u2014 commonly 15\u201320 K higher discharge temperature for the same evaporating and condensing conditions, because of R-32&#8217;s higher compression discharge characteristics.<\/p>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Condition<\/th><th>Typical R-410A discharge temp<\/th><th>Typical R-32 discharge temp<\/th><\/tr><\/thead><tbody><tr><td>Moderate load, normal ambient<\/td><td>75\u201385\u00b0C<\/td><td>90\u2013105\u00b0C<\/td><\/tr><tr><td>High ambient, high load (Cape Town summer peak)<\/td><td>90\u2013105\u00b0C<\/td><td>110\u2013125\u00b0C<\/td><\/tr><tr><td>Approaching compressor protection limit<\/td><td>~130\u2013135\u00b0C<\/td><td>Reached sooner, often 15\u201320 K below the R-410A figure for the same conditions<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Because R-32 starts from a higher discharge baseline, it has a smaller thermal margin before hitting the compressor manufacturer&#8217;s maximum discharge temperature limit. This is one reason many R-32 compressors ship with tighter factory-set discharge temperature protection, and why manufacturers are stricter about minimum superheat on R-32 equipment than they were on equivalent R-410A units.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Why Low Superheat Is More Damaging on R-32<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Low superheat is a problem on any refrigerant because of floodback risk, but on R-32 it compounds with the discharge temperature margin already being smaller. A floodback event that dilutes oil and drops discharge temperature protection headroom by even 10 K is a bigger percentage bite out of a smaller safety margin on R-32 than the same event would be on R-410A. Hold superheat within 1 K of the manufacturer&#8217;s target on R-32 equipment specifically \u2014 don&#8217;t treat &#8220;close enough&#8221; as tolerable at the low end the way you might have gotten away with on some R-410A installations, because the discharge temperature consequence arrives faster.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">A2L Classification: What Changes in Handling<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">R-32 is classified A2L \u2014 mildly flammable, lower toxicity \u2014 which is a genuine change from R-410A&#8217;s non-flammable classification, and it changes practical handling on site:<\/p>\n\n\n\n<ol class=\"wp-block-list\"><li><strong>Leak detection equipment must be rated for A2L refrigerants.<\/strong> A standard halide or non-specific electronic sniffer calibrated for R-410A may not reliably detect R-32 at the concentrations that matter \u2014 confirm your detector is rated for the refrigerant you&#8217;re checking.<\/li><li><strong>No brazing or open flame work near a suspected or confirmed leak<\/strong> until the space has been ventilated and confirmed clear. This is a firm sequencing change from R-410A practice, where ignition risk wasn&#8217;t part of the leak-repair decision.<\/li><li><strong>Room charge limits apply.<\/strong> A2L equipment is designed and labelled with a maximum permissible refrigerant charge relative to the installed room&#8217;s volume, to keep any full-charge release below a flammable concentration. Check the equipment&#8217;s charge limit label before adding refrigerant or relocating equipment into a smaller space than it was designed for \u2014 don&#8217;t assume a charge amount that was fine on an R-410A system in the same space is automatically fine on an A2L system.<\/li><li><strong>Recovery and service equipment should be A2L-compatible<\/strong> where required by the equipment or local regulation \u2014 recovery machines, hoses, and gauges rated for flammable refrigerants, not repurposed non-flammable-only equipment.<\/li><li><strong>Ventilation before and during service work<\/strong> in confined plant rooms is a more active requirement than it was for R-410A, where the only atmospheric concern was oxygen displacement rather than flammability.<\/li><\/ol>\n\n\n\n<h2 class=\"wp-block-heading\">Never Mix Refrigerants<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">R-410A is itself half R-32 by mass, which sometimes leads to the mistaken assumption that topping up an R-410A system with R-32, or vice versa, is a minor deviation. It isn&#8217;t. Mixing changes the blend ratio in ways that alter the pressure-temperature relationship unpredictably, invalidates your superheat and subcooling targets because they were set for a specific composition, and on a system not designed and labelled for a flammable refrigerant, introduces an ignition risk the equipment was never engineered to manage. Always confirm the refrigerant type from the equipment nameplate and any service history before connecting a cylinder, recover to a correctly labelled cylinder dedicated to that refrigerant, and never assume compatibility because two refrigerants share a component.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">What Changes and What Doesn&#8217;t<\/h2>\n\n\n\n<figure class=\"wp-block-table\"><table><thead><tr><th>Aspect<\/th><th>Changes between R-410A and R-32?<\/th><th>Detail<\/th><\/tr><\/thead><tbody><tr><td>Superheat and subcooling formulas<\/td><td>No<\/td><td>Same calculation, same targets from equipment data<\/td><\/tr><tr><td>Glide handling<\/td><td>No<\/td><td>Both negligible in the field; neither needs dew\/bubble point math<\/td><\/tr><tr><td>Pressure-temperature relationship<\/td><td>Minor<\/td><td>Within about 5% at a given temperature \u2014 use the correct chart, don&#8217;t estimate<\/td><\/tr><tr><td>Discharge temperature<\/td><td>Yes, significantly<\/td><td>15\u201320 K higher on R-32 at comparable conditions<\/td><\/tr><tr><td>Tolerance for low superheat<\/td><td>Yes<\/td><td>Tighter on R-32 due to reduced discharge temperature margin<\/td><\/tr><tr><td>Leak detection and ignition handling<\/td><td>Yes<\/td><td>A2L-rated equipment and no-flame-until-clear sequencing required<\/td><\/tr><tr><td>Room charge limits<\/td><td>Yes<\/td><td>Governed by flammability, not just refrigeration capacity<\/td><\/tr><tr><td>Mixing refrigerants<\/td><td>No change \u2014 always prohibited<\/td><td>Applies equally to both, and to any refrigerant pairing<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">Final Thoughts<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The superheat and subcooling method you already know carries over from R-410A to R-32 without modification, and neither refrigerant&#8217;s small or absent glide requires dew and bubble point calculations. What changes is discharge temperature \u2014 meaningfully higher on R-32, which shrinks the compressor&#8217;s thermal safety margin and makes tight superheat control more important, not less \u2014 and the A2L handling requirements that come with a mildly flammable refrigerant. For the underlying comparison of what each reading tells you, see <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/superheat-vs-subcooling-which-one-tells-you-what\/\">superheat vs subcooling: which one tells you what<\/a>, and for the subcooling measurement procedure referenced throughout this article, see <a href=\"https:\/\/www.paradigmcooling.co.za\/articles\/how-to-measure-subcooling-and-what-it-tells-you\/\">how to measure subcooling and what it tells you<\/a>. The complete diagnostic framework is covered in the <a href=\"https:\/\/www.paradigmcooling.co.za\/hvacr-learning-library\/understanding-superheat-and-subcooling-the-complete-guide-to-refrigerant-charging-diagnostics-and-hvacr-system-performance\/\">complete guide to superheat and subcooling<\/a>.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>R-32 is replacing R-410A across much of the split and light commercial market, and the good news for a working technician is that the diagnostic [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[19,37],"tags":[],"class_list":["post-4496","post","type-post","status-publish","format-standard","hentry","category-refrigeration","category-superheat-and-subcooling"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.7 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;<\/title>\n<meta name=\"description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"og:description\" content=\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/\" \/>\n<meta property=\"og:site_name\" content=\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/www.facebook.com\/Paradigm-Cooling\" \/>\n<meta property=\"article:published_time\" content=\"2026-10-13T09:00:00+00:00\" \/>\n<meta name=\"author\" content=\"Paradigm Cooling\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:creator\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:site\" content=\"@ParadigmCooling\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"Paradigm Cooling\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"7 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/\"},\"author\":{\"name\":\"Paradigm Cooling\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"headline\":\"Superheat and Subcooling on R-32 and R-410A: What Changes\",\"datePublished\":\"2026-10-13T09:00:00+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/\"},\"wordCount\":1413,\"commentCount\":0,\"articleSection\":[\"Refrigeration\",\"Superheat and Subcooling\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/\",\"name\":\"Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\"},\"datePublished\":\"2026-10-13T09:00:00+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\"},\"description\":\"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/2026\\\/10\\\/13\\\/superheat-readings-on-r32-and-r410a\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Superheat and Subcooling on R-32 and R-410A: What Changes\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#website\",\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/\",\"name\":\"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;\",\"description\":\"Engineered Comfort\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/#\\\/schema\\\/person\\\/aa8620838017ae91189e084f478f6d02\",\"name\":\"Paradigm Cooling\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"url\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"contentUrl\":\"\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/wp-content\\\/cache\\\/speedycache\\\/www.paradigmcooling.co.za\\\/gravatars\\\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg\",\"caption\":\"Paradigm Cooling\"},\"sameAs\":[\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\"],\"url\":\"https:\\\/\\\/www.paradigmcooling.co.za\\\/articles\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/","og_locale":"en_US","og_type":"article","og_title":"Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","og_description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","og_url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/","og_site_name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","article_publisher":"https:\/\/www.facebook.com\/Paradigm-Cooling","article_published_time":"2026-10-13T09:00:00+00:00","author":"Paradigm Cooling","twitter_card":"summary_large_image","twitter_creator":"@ParadigmCooling","twitter_site":"@ParadigmCooling","twitter_misc":{"Written by":"Paradigm Cooling","Est. reading time":"7 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/#article","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/"},"author":{"name":"Paradigm Cooling","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"headline":"Superheat and Subcooling on R-32 and R-410A: What Changes","datePublished":"2026-10-13T09:00:00+00:00","mainEntityOfPage":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/"},"wordCount":1413,"commentCount":0,"articleSection":["Refrigeration","Superheat and Subcooling"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/","url":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/","name":"Superheat and Subcooling on R-32 and R-410A: What Changes - &quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","isPartOf":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website"},"datePublished":"2026-10-13T09:00:00+00:00","author":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02"},"description":"Paradigm Cooling answering the most frequently asked HVAC and refrigeration related questions.","breadcrumb":{"@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/2026\/10\/13\/superheat-readings-on-r32-and-r410a\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.paradigmcooling.co.za\/articles\/"},{"@type":"ListItem","position":2,"name":"Superheat and Subcooling on R-32 and R-410A: What Changes"}]},{"@type":"WebSite","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#website","url":"https:\/\/www.paradigmcooling.co.za\/articles\/","name":"&quot;Paradigm Cooling: Your Go-To HVAC &amp; Refrigeration Blog for Common Technical Questions&quot;","description":"Engineered Comfort","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.paradigmcooling.co.za\/articles\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Person","@id":"https:\/\/www.paradigmcooling.co.za\/articles\/#\/schema\/person\/aa8620838017ae91189e084f478f6d02","name":"Paradigm Cooling","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","url":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","contentUrl":"\/\/www.paradigmcooling.co.za\/articles\/wp-content\/cache\/speedycache\/www.paradigmcooling.co.za\/gravatars\/c876ae2f7899ba3b5ad7eac3bec0af3cx96.jpg","caption":"Paradigm Cooling"},"sameAs":["https:\/\/www.paradigmcooling.co.za\/articles"],"url":"https:\/\/www.paradigmcooling.co.za\/articles\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4496","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/comments?post=4496"}],"version-history":[{"count":1,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4496\/revisions"}],"predecessor-version":[{"id":4897,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/posts\/4496\/revisions\/4897"}],"wp:attachment":[{"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/media?parent=4496"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/categories?post=4496"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.paradigmcooling.co.za\/articles\/wp-json\/wp\/v2\/tags?post=4496"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}